VPS 504 Dungs: Control de Estanqueidad is the valve proving system for DUNGS multiple actuators. The valve proving system complies with EN 1643:

  1. Equipment operates independent of residual pressure in the range of the permissible operating range.
  2. Test volume ≤ 4 l
  3. Setting work not necessary on site
  4. Short test period: min. 10 s, max. 26 s
  5. Tightness or leaks are displayed by an LED
  6. External fault display possible for series 02, series 04 and S05
  7. Group fault alarm optional for S01 (SSM)
  8. Suitable for TRD systems
  9. Electrical connection possible by plug connection S01, 02, 03. No rewiring is required for contact allocation as per DIN 4791.
  10. S04 and S05: electrical connection at screw terminals via PG 13.5 cable entry

VPS 504 Valve proving system for automatic shutoff valves as per EN 161, Class A and Class B The VPS 504 may be used with any other valve whose tightness in counter-flow direction excludes by construction a leakage in flow direction. The VPS 504 is suitable for all DUNGS valves according to EN 161 Classes A and B.

Aplicaciones de VPS 504 Dungs: Control de Estanqueidad

  1. Valve proving system for DUNGS single valves, DMV double solenoid valve and GasMultiBloc MB.
  2. The VPS 504 can also be used for monitoring the DUNGS solenoid valves up to DN 80, with and without bypass connection. 24 VDC design for gas motors.
  3. Suitable for gases of gas families 1, 2, 3 and other neutral gaseous media.
  1. EC type test approval as per EC Gas Appliance Directive:
  2. VPS 504… CE-0085 AP 0168 EC type test approval as per EC Pressure Equipment Directive:
  3. VPS 504… CE0036 Approvals in other important gas consuming countries. Special design for the North American market with UL, FM and CSA registration.

Ficha técnica– Click aquí

Instrucciones de operación y montaje– Click aquí

Productos Relacionados – ● VPS S06 Dungs: Control De Estanqueidad ● Señalizador De Posición De Válvulas Dungs- Serie K01/1 MV 502: Válvula De Gas De Ignición – Dungs ● Válvula De Prueba Para Manometros – Dungs

VPS 504 Dungs: Control de Estanqueidad de venta aquí, contacta a alguno de nuestros asesores dentro del chat o marca al número de sucursal más cercano a ti, será un placer atenderte.

📌 Tabla de Selección

VPS 504 type overview / accessories / order data
Version VPS 504 Series …
Nominal voltage, Frequency 20-30 VDC 230 V 220 V 120 V 110 V
-15% -15% -15% -15%
240 V 10% 10% 10%
6% 60 Hz 60 Hz 50 Hz
50 Hz
VPS 504 S01 222 390 223 464
7-pole plug connection Cable length: 0.30 m 219 873
Wiring as per DIN 4791 Cable length: 0.85 m 219 874
IP 40 degree of protection Cable length: 1.50 m 219 875
Cable length: 2.00 m 219 876
Group fault alarm Cable length: 0.85 m 227 462
Group fault alarm Cable length: 2.00 m 227 527
VPS 504 S02

with male connector

with male connector, CSAC,UC

without male connector

with male connector

225 481 222 389 223 463
7-pole plug connection 219 877
7-pole plug connection
Free connection 219 878
IP 40 degree of protection
Liquefied gas model 226 315
VPS 504 S03 Cable length: 1.50 m 223 590
7-pole plug connection
Wiring as per DIN 4791
IP 40 degree of protection
VPS 504 S04 219 881 222 388 223 426 221 327
Connection to screw terminals
PG 13.5 cable duct
Additionally, PG 11 possible
Floating fault signal (control room signal)
IP 54 degree of protection
Liquefied gas model 226 316 242 874 242 875 242 876
VPS 504 S05 (Gasmotors) CSAC,UC 224 983
VPS 504 S06 UL, FM, CSA 221 073
Accessories/spare parts
Adapter kit VPS 504 for solenoid valves up to Rp 2 205 360
Adapter kit VPS 504 for solenoid valves from DN 40 to DN 80 222  740
Adapter kit VPS / VDK 223  470
7-pole male connector, 2 cable inputs with strain relief (S02) 231 807
7-pole male connector, 4 cable inputs with PG 11 (S02) 231 808
7-pole male connector, 4 cable inputs with strain relief (S02) 231 809
Mounting kit (4 x M4 x 16,2, 2 x O-Ring, 2 x filter insert) 221 503
Appliance fuse link (5 pieces) 231 780
Spare parts set VPS filter 243 801

 

📋 Especificaciones básicas

Operating pressure max. 500 mbar (50 kPa)
Test volume ≥ 0.1 l ≤ 4.0 l
Pressure increase by motor pump ≈ 20 mbar
Nominal voltage, Frequency refer to type overview page 11
Rating requirement During pumping time approx. 60 VA, in operation 17 VA
Prefuse (provided by customer) A quick-acting or 6.3 A slow-acting fuse
Fuse installed in housing cover, replaceable Microfuse 6.3 slow-blow L 250 V; IEC-127-2/III (DIN 41 662)
Switching current Operating output VPS 504 S01, 02, 03, 04, 05: max. 4 A Refer to motor startup current! Interference output VPS 504 S02, 04, 05:  max.1A
Degree of protection VPS 504 S01, 02, 03:    IP 40 VPS 504 S04, 05:    IP 54
Ambient temperature Hz 230 VAC  -15°C to +70°Cothers:    -15°C to +60°C
Release time Approx. 10 – 26 s, depending on test volume and input pressure
Sensitivity limit max. 50 l/h
At inlet pressures of < 50 mbar, limit pressure rates well below 50 l of air per hour occur due to the mode of operation. This allows for applications involving low inlet pressures.
Switch-on duration of control 100% ED
Max. number of test cycles 20/h. Wait for at least 2 minutes after carrying out more than 3 consecutive test cycles.
Installation position vertical, horizontal, not upside down
Media
•  Standard model Gas families 1, 2, 3, sewage gas, landfill gas and biogas (dry, H2S < 0.1% by volume) and other gaseous media Not for gases having a butane content of > 60%
•  Liquefied gas model Gas family 3 and gases having a butane content of > 60%, gases having a density of > 1 kg/m3

 

✔️ Aplicaciones de producto

Valve proving system for DUNGS single valves, DMV double solenoid valve and GasMultiBloc MB.

The VPS 504 can also be used for monitoring the DUNGS solenoid valves up to DN 80, with and without bypass connection. 24 VDC design for gas motors.

Suitable for gases of gas families 1, 2, 3 and other neutral gaseous media.

📑 Ficha técnica


219547.pdf (951 KB)

👷 Instrucciones de operación y montaje.


223937.pdf (3 MB)
219550.pdf (3 MB)

✔️ Certificación

AGA-5272.pdf (323 KB)
CE-0085AP0168.pdf (389.2kB)
DGR-009.pdf (430.1kB)
EAC-Valve-Proving-Systems.pdf (163 KB)
Ventilpruefsysteme.pdf (1,004 KB)

🎥 Video

 

Valoraciones

No hay valoraciones aún.

Sé el primero en valorar “VPS 504 Dungs: Control de Estanqueidad”

Tu dirección de correo electrónico no será publicada. Los campos obligatorios están marcados con *

Visitanos en Redes Sociales

Sígueme en Facebook Sígueme en Facebook Sígueme en Flickr! Sígueme en instagram! Sígueme en youtube!
es_MXSpanish
0
    0
    Your Cart
    Your cart is emptyReturn to Shop
    jQuery(document).ready(function ($) {n var ajaxurl = \'<?php echo admin_url(\'admin-ajax.php\'); ?>\';n $(\'.brands_form #modal_marques\').on(\'select2:select\', function (e) {n $(\'.brands_form .keyword\').append("<span style=\'color: black\' class=\'fa fa-spinner fa-spin\'></span>");n $(\'.brands_form .brands .select2-selection__arrow\').hide();n var brands = $(\'.brands_form #modal_marques\').find(\':selected\').data(\'id\');n $.ajax({n type: "POST",n url: ajaxurl,n data: {n action: "ajzaa_products_model",n brands: brandsn },n success: function (data) {n $(\'.brands_form #modal_models\').html(data);n $(".keyword .fa-spinner").remove();n $(\'.brands_form .brands .select2-selection__arrow\').show();n $(\'#modal_models\').select2(\'open\');n },n error: function (errorThrown) {n alert(errorThrown);n }n });n });n $(\'.brands_form #modal_models\').on(\'select2:select\', function (e) {n $(\'.brands_form .year\').append("<span style=\'color: black\' class=\'fa fa-spinner fa-spin\'></span>");n $(\'.brands_form .keyword .select2-selection__arrow\').hide();n var modal_years = $(\'.brands_form #modal_models\').find(\':selected\').data(\'id\');n $.ajax({n type: "POST",n url: ajaxurl,n data: {n action: "ajzaa_products_years",n years: modal_yearsn },n success: function (data) {n $(\'.brands_form #modal_year\').html(data);n $(".year .fa-spinner").remove();n $(\'.brands_form .keyword .select2-selection__arrow\').show();n $(\'#modal_year\').select2(\'open\');n },n error: function (errorThrown) {n alert(errorThrown);n }n });n });nn });